Development and Experimental Evaluation of an Integrated Virtual Instrumentation System for Arc Flash Incident Energy Measurement
DOI:
https://doi.org/10.18618/REP.e202644Keywords:
Arc flash, IEEE 1584, Incident energy, Temperature measurement, Virtual instrumentationAbstract
Experimental determination of incident energy (IE) in arc flash testing requires integrating calorimetry, signal acquisition, and thermal processing; when performed separately, these tasks may increase operator intervention and hinder data-flow standardization. This study developed and experimentally evaluated an integrated system for IE measurement in arc flash tests. The architecture combines copper calorimeters instrumented with Type K thermocouples and arranged according to the spatial configuration adopted in the IEEE Std 1584-2018 test program, galvanically isolated data acquisition, and a LabVIEW-based virtual instrument (VI) for monitoring, thermal-parameter identification, Shomate-based enthalpy calculations, and data storage. The calorimeters satisfied the functional-verification criterion of IEC 61482-1-1, and the VI-based IE calculation showed numerical agreement with an independently implemented reference calculation. Across 18 tests, comprising 10 tests with vertical electrodes in open air (VOA) and 8 with horizontal electrodes in open air (HOA), measured IE remained below the corresponding IEEE Std 1584-2018 estimates, with relative differences from -29.3 % to -2.6 % and a mean of -12.7 %. This ordering was consistent under the evaluated conditions, although the magnitude of the difference varied among tests and should not be generalized beyond the investigated experimental set. The proposed integration consolidates calorimetric IE acquisition, processing, and comparison into a single workflow.
Downloads
References
A. D. Stokes and W. T. Oppenlander, “Electric Arcs in Open Air,” Journal of Physics D: Applied Physics, vol. 24, no. 1, pp. 26–35, 1991, doi: 10.1088/0022-3727/24/1/006.
R. H. Lee, “The Other Electrical Hazard: Electric Arc Blast Burns,” IEEE Transactions on Industry Applications, vol. IA-18, no. 3, pp. 246–251, 1982, doi: 10.1109/TIA.1982.4504068.
IEEE Guide for Performing Arc-Flash Hazard Calculations, IEEE Std 1584-2018 (Revision of IEEE Std 1584-2002). Piscataway, NJ, USA: IEEE, Nov. 2018, pp. 1–134, doi: 10.1109/IEEESTD.2018.8563139.
NFPA, NFPA 70E: Standard for Electrical Safety in the Workplace, 2027 ed. Quincy, MA, USA: National Fire Protection Association, 2026.
Brazil, Ministry of Labor and Employment, “Portaria MTE No. 737, de 29 de maio de 2026: Aprova a nova redação da Norma Regulamentadora No. 10 (NR-10)—Segurança em Instalações Elétricas e Serviços em Eletricidade,” Diário Oficial da União, ed. 101, sec. 1, p. 167, Jun. 1, 2026.
ASTM International, ASTM F1959/F1959M-24b: Standard Test Method for Determining the Arc Rating of Materials for Clothing. West Conshohocken, PA, USA: ASTM International, 2024.
IEC 61482-1-1, Live Working—Protective Clothing Against the Thermal Hazards of an Electric Arc—Part 1-1: Test Methods—Method 1: Determination of the Arc Rating (ELIM, ATPV and/or EBT50) of Clothing Materials and Protective Clothing Using an Open Arc, IEC Standard 61482-1-1, Edition 2.0, Geneva, Switzerland, 2019.
P. O. Bacin et al., “Infrared Thermography for Incident Energy Measurement in Arc Flashes under VOA Configuration Supported by Statistical Analysis,” in 2025 IEEE ESW Brazil – Electrical Safety Workshop Brazil (ESW Brazil), São Paulo, Brazil, 2025, pp. 1–8, doi: 10.1109/ESWBrazil64921.2025.11277734.
M. Bottaro, L. E. Caires, P. F. Obase, T. O. de Carvalho, and H. Tatizawa, “A Comprehensive Analysis of the Influence of Thermal Insulating Materials on Arc Rating Tests,” IEEE Transactions on Instrumentation and Measurement, vol. 74, Art. no. 1500609, pp. 1–9, 2025, doi: 10.1109/TIM.2025.3529562.
ASTM Committee E20 on Temperature Measurement, Manual on the Use of Thermocouples in Temperature Measurement, R. M. Park, Ed., 4th ed., ASTM MNL12, Revision of ASTM STP 470B. West Conshohocken, PA, USA: ASTM International, 1993, doi: 10.1520/MNL12-4TH-EB.
N. Henderson, “Practical Temperature Measurements,” Application Note, VTI Instruments, AMETEK Programmable Power, San Diego, CA, USA. [Online]. Available: https://www.vtiinstruments.com/knowledge-center/white-papers
Z. Zhang, W.-J. Lee, and D. A. Dini, “Grounding and Isolation of Sensitive Measurement Equipment for Arc Flash Testing at High-Power Laboratory,” IEEE Transactions on Industry Applications, vol. 51, no. 6, pp. 5281–5287, Nov./Dec. 2015, doi: 10.1109/TIA.2015.2411654.
F. C. S. Soares et al., “Measurement of Arc Flash Incident Energy in Low-Voltage Three-Phase Panels Using an Optical Calorimeter,” in 2025 IEEE ESW Brazil – Electrical Safety Workshop Brazil (ESW Brazil), São Paulo, Brazil, 2025, pp. 1–5, doi: 10.1109/ESWBrazil64921.2025.11277722.
M. W. Chase, Jr., NIST-JANAF Thermochemical Tables, 4th ed., J. Phys. Chem. Ref. Data, Monograph No. 9. Washington, DC, USA: American Chemical Society, 1998. ISBN: 978-1-56396-831-0.
M. Bottaro, Instrumentação Virtual em Laboratório: Introdução ao LabVIEW, São Paulo, Brasil: Instituto de Eletrotécnica e Energia da Universidade de São Paulo (IEE-USP), 2012, 125 p., ISBN: 978-85-86923-27-2.
A. A. S. Pereira et al., “Metodologia de Instrumentação e Medição da Energia Incidente de Arcos Elétricos por Termopares,” in Proceedings of the 17th Seminar on Power Electronics and Control (SEPOC 2025), 2025, doi: 10.53316/sepoc2025.002.
P. O. Bacin et al., “Incident Energy Determination of Three-Phase Arc Flash Using Magnetohydrodynamics Simulations: A Case Study for Horizontal Electrodes in Open-Air Configurations,” High Voltage, vol. 10, no. 2, pp. 436–450, 2025, doi: 10.1049/hve2.70009.
F. C. S. Soares et al., “Development of an Optical Calorimeter Sensor for the Arc Thermal Performance Value (ATPV) Determination on Arc-Rated Materials for Personal Protective Equipment,” Sensors, vol. 26, no. 8, p. 2352, 2026, doi: 10.3390/s26082352.
P. O. Bacin, “Contribuição ao desenvolvimento de um laboratório de arcos elétricos para a medição da energia incidente,” M.S. thesis, Graduate Program in Electrical Engineering, Federal University of Santa Maria, Santa Maria, RS, Brazil, 2022. URL: https://repositorio.ufsm.br/handle/1/26218.
C. S. Mardegan, F. B. Resende, and M. Bottaro, Arco Elétrico e Energia Incidente: Metodologias de Cálculo em Sistemas AC e DC, EPIs, EPCs, Técnicas para Redução da EI e Equipamentos e Dispositivos para Melhorar a Segurança. 1st ed. São Paulo, SP, Brasil: Ed. do Autor, 2025, ISBN: 978-65-01-41915-2.
L. M. R. Baccarini, B. R. de Menezes, L. H. Batista, and W. M. Caminhas, “Identificação de Falhas Utilizando Informações de Sensores Presentes no Quadro de Comando dos Motores,” Eletrônica de Potência, vol. 17, no. 4, pp. 763–770, Nov. 2012, doi: 10.18618/REP.2012.4.763770.
S. A. O. da Silva, D. H. Wollz, and L. P. Sampaio, “Development of a Didactic Workbench Using Real-Time Monitoring System for Teaching of Photovoltaic Systems,” Eletrônica de Potência, vol. 23, no. 3, pp. 371–381, Sep. 2018, doi: 10.18618/REP.2018.3.2793.
National Instruments, LabVIEW, Austin, TX, USA. [Online]. Available: https://www.ni.com/labview
W.-J. Lee, T. L. Gammon, and Z. Zhang, “Systems and Methods for Arc Flash Hazard Assessment,” U.S. Patent 9,146,267 B2, Sep. 29, 2015.
IEEE Standards Association, “Arc Flash IE and Iarc Calculators,” IEEE DataPort Dataset, Dec. 19, 2019, doi: 10.21227/8gch-a963.
Downloads
Published
How to Cite
Issue
Section
License
Copyright (c) 2026 Andrey A. S. Pereira, Pedro O. Bacin, Vitor C. Bender, Marcio Bottaro, Tiago B. Marchesan, Gilnei J. G. dos Santos, Jéssica P. Begossi